P2 and c2 connect to a separate all metallic grounding point like a water pipe or building steel.
Ground rod resistance formula.
R1 resistance of one ground rod n total rods in layout k combining factor rn total net resistance of grounding system r measured earth to ground resistance using ieee 4 point method p 38 30 r for 10 ground rods 19 15 r or 38 30 r for 20 ground rods k 378 log n 89.
Hi slamat thank you for your question regarding resistance to ground calculations for parallel electrodes it is our pleasure to help.
Multiple ground rods yield a lower resistance to ground than a single rod.
Earthing resistance and number of rods for isolated earth pit without buried earthing strip the earth resistance of single rod or pipe electrode is calculated as per bs 7430.
Step 1 connect your length of wire to a metal stake in the ground.
The simplified calculation for predicting the resistance to ground earth of a given length grounding rod is.
You should measure the resistance of an electrode with respect to the surrounding soil in the area.
L total length grounding grid conductors 4 x 200 6 x 150 6 x 50 2000 meters.
In areas where driving ground rods may be impractical the two point method can be used.
If this is the case for your ground rod the best solution is to drive a different rod into a different location.
In some instances ground rods can be installed in areas where the earth has a lot of resistance.
R p 2 pi l ln 4l a 1 p 2 pi s 1 l squared 3s 10x8 2l 10 4 5s 10 4 where.
Make sure that you have stripped back the insulation from both ends of the wire to allow for a good connection.
If your ground rods are placed at least one rod length apart you can use a formula to estimate the earth resistance of multiple grounding rods.
However we can estimate the resistance to ground using scenario b.
Ground ring ground rods.
For example the national electric code requires no greater than 25 ohms of resistance in a ground system.
R resistance p soil resistivity l length.
Calculate the upper limit of ground resistance rg of the grid if soil resistivity is 180 ω m for a ground grid shown in below figure.
The total burial length is the combination of the horizontal and vertical conductors in the grid as well as the ground rods.
R ρ 2 3 14xl loge 8xl d 1 where.
For instance if a ground rod is driven into a very rocky and dry area it may not conduct electricity into the ground well.
So if you are using 10 foot ground rods you must place.
Use the above formula to approximate the ground resistance of a system and not as a replacement for actual ground measurements.
Run the wire to your test location.
With this method the resistance of two electrodes in a series is measured by connecting the p1 and c1 terminals to the ground electrode under test.